FISHER FISHER valve DVC6000 debugging steps

Time:12-01

Open 275/375 hand operator (the MainMenu) from the main menu select Hart application (HARTApplication) from the Online to find the accessories, in turn into Setup& Diag - DetailedSetup - Mode - InstumentMode (or by hand on shortcut directly into) - warning! When the valve of inservice mode be sent to the instrument may be moved (WARNING! ValvemaymovewheninServicemodeissenttotheinstrument,) after press OK to ENTER the instrument model (InstrumentMode) press ENTER - after choosing Outofservice Instrumentmodeisalreadyoutofservice! "" After the return to the main interface in turn into Setup& Diag - BasicSetup Autosetup -- SetupWizard:
1, select the pressure you use unit (Pressureunits (psi)) after ENTER;
2, the input gas pressure (MaxSupplyPress (psi)) after ENTER;
3, select the manufacturer of the actuator (ActuatorManufcture) ENTER brand or not after the OTHER;
4, if a single acting actuator with spring to choose 3, double-acting spring choose 4, double-acting without spring to choose 2;
5, choose the ROTARY valve according to zero next signal is open to choose 2 close to choose 1 re-election next next YES to and gain size automatically choose the valve;
6, choose whether to have the accelerator or the quick release valve (IsaVolumeBoosterorQuickReleasePresent?) ;
7, the tip of the actuator information is being sent to the instrument, please wait a moment "Actuatorinformationisbeingsenttotheinstrument, Pleasewait..." ;
UseFactorydefaultsforsetup 8, choose to use the factory default Settings? After (YesisrecommendedforInitialSetup) Yes ENTER;
9, prompt the factory default Settings are being sent to the instrument, please wait a moment "Factorydefaultarebeingsenttotheinstrument, Pleasewait..." ;
10, continue to adjust automatically set to select amplifier "TocontinueAutoSetup, selecRelayAdjust";
11, would you like to adjust amplifier now? (DoyouwishtorunRelayAdjustmentCalibrationnow? Select Yes if be double single role after select No ENTER;
12, select the calibration schedule (Tocontinue selecAutoCalibTravel, click OK;
13, do you want for automatic calibration now? (DoyouwishtorunAutoTravelCalibnow? Press ENTER after selecYESifinitialsetup) select Yes;
14, warning! Calibration will cause the sudden change the output of the press OK instrument;
15, select the adjustment of the intersection (selecCrossoverAdjust) Manual/LastValue/Default choice normally ENTER after the Default if the Default adjusted with poor accuracy will select Manual Manual;
16, into the process of automatic calibration schedule below, after the completion of the meter mode back to Inservice!